info@ogontz.com 800-523-2478

Design Features

  • 200 psig (maximum operating pressure)
  • Conserves energy
  • Minimizes flash and live steam losses
  • Freeze protected — self draining
  • Maintains temperature set point at any pressure
  • Back pressure insensitive
  • Throttles down to 1/2 pound per hour for extremely light loads
  • 100% factory tested

Unit of Measure

Specifications

NPT Inlet Thread Size

N/A 1/2 in

NPT Outlet Thread Size

N/A 1/2 in

Valve Type

N/A CTV Steam Trap Valve

Condensate Discharge Temperature Range

N/A 35 to 240 ºF

Maximum Operating Pressure

N/A 200 psig

Flow Coefficient (Cv)

N/A 0.17

Valve Action

N/A Direct

Body Material

N/A Tubular Stainless Steel

Dimensional Drawing

N/A
CTV Schematic Figure 1

Net Weight

N/A 3/4 lb

Note

N/A Actual temperature settings would depend upon the requirements and variables of your specific application. A 180°F setting, for example, is ideal for most winterization systems; a 240°F setting is suggested for most process tracing and drip legs. For impulse and sample lines, a 60°F or 120°F setting could be used. To be used in saturated steam systems only. Valve will slowly actuate within a 15°F differential of specified setpoint.

The Ogontz Guarantee

N/A We will repair or replace on a no-charge basis, FOB Willow Grove, PA, any valves or traps returned to us within 18 months, if found to be defective in material or workmanship.