Print Back
The FP/FPR series valves feature a space-saving, in-line design and high/low temperature sensitivity to provide positive freeze/scald protection for emergency safety showers and eyewash stations.Freeze ProtectionThe low temperature actuated FP series provides the same basic freeze protection as the F/FG series valves, but with a straight-through flow area larger than the pipe diameter for unrestricted flow.Scald ProtectionThe reverse acting FPR series valve is actuated by temperatures in excess of 100°F due to overheating, direct sunlight or other heat source. Discharge stops when temperature drops below 90°F. Full flow to shower head is also assured.

Note: Specify temperature between 35° and 255°F in 5°F increments. Differential from full open to full closed is typically 10° to 15°F. Valve opens/closes gradually.

Unit of Measure

Specifications

NPT Thread Size

1-1/4 in

Valve Type

FPR Series Scald Protection Valve

Port Size

1/4 in

Maximum Operating Pressure

200 psig

Flow Coefficient (Cv)

1.0

Valve Action

Reverse

Body Material

Bronze

Dimensional Drawing


FP/FPR Schematic Figure 1
Dimension A1 4-1/4 in
Dimension B2 5-1/4 in
Dimension C3 2 in

Net Weight

4 lb

The Ogontz Guarantee

We will repair or replace on a no-charge basis, FOB Willow Grove, PA, any valves or traps returned to us within 18 months, if found to be defective in material or workmanship.

Plug Material

PTFE Silicone

Optional Standard Leak Ports

LX - 1/4 to 1/2 GPM at 60 PSIG LZ - 1/2 to 1 GPM at 60 PSIG
  • 1 ±1/8 in Tolerance
  • 2 ±1/8 in Tolerance
  • 3 ±1/8 in Tolerance