Print Back

                                                                                   












Design Features

  • 200 psig (maximum operating pressure)
  • High flow capacity
  • Back pressure insensitive
  • Freeze protected — self draining
  • Maintains temperature set point
  • 100% factory tested
Benefits
  • Easy installation
  • Reliable, unattended operation
  • Minimal maintenance requirements
  • Conserves energy
  • Minimizes flash and live steam loss

Unit of Measure

Specifications

NPT Inlet Thread Size

1/2 in

NPT Outlet Thread Size

1/2 in

Valve Type

CAT Condensate Actuated Temperature Control Valve

Maximum Operating Pressure

200 psig

Flow Coefficient (Cv)

2

Valve Action

Direct

Body Material

303 Stainless Steel

Dimensional Drawing


CAT Schematic Figure 1

Net Weight

3/4 lb

Note

Actual temperature settings would depend upon the requirements and variables of your specific application. A 180°F setting, for example, is ideal for most winterization systems; a 240°F setting is suggested for most process tracing and drip legs. For impulse and sample lines, a 60°F or 120°F setting could be used. Not suitable for superheated steam systems. Valve will slowly actuate with a 15°F differential of specified setpoint.

The Ogontz Guarantee

We will repair or replace on a no-charge basis, FOB Willow Grove, PA, any Ogontz product returned to us within 18 months, if found to be defective inmaterial or workmanship.